UPONOR CONTROL SYSTEM KNX INTERFACE MANUAL - CONNECTING UPONOR CONTROLLER C-56 WITH MEDIA COUPLER TR131A/B
8
5.2 Data point list per controller C-56
5.3 Data point list per system
HVAC Mode Current control mode: Comfort, ECO, or Frost
protection
DPT_HVACMode R R R
Relative Humidity From wireless RH sensor DPT_Value_
Humidity
Valid if RH sensor is
linked
RR R/W
Tamper Alarm 0 = No alarm, 1 = Alarm DPT_Alarm Valid if T-54 is
linked
RR R
Technical Alarm Option if Uponor Thermostat T-53 is used DPT_Alarm Valid if T-53 is
linked
RR R
Parameter name Explanation KNX data type Display condition Read
only
Limited
write
access
Full
access
Parameter name Explanation KNX Data type Read
only
Limited
write
access
Full
access
Boiler Status Reflects the status of the boiler control relay.
0 = Open, 1 = Closed
DPT_Switch R R R
Pump Status Reflects the status of the pump control relay.
0 = Open, 1 = Closed
DPT_Switch R R R
Supply Alarm High 0 = No alarm, 1 = Alarm DPT_Alarm R R R
Supply Alarm Low 0 = No alarm, 1 = Alarm DPT_Alarm R R R
Parameter name Explanation KNX data type Read
only
Limited
write
access
Full
access
Autobalancing Activation Activates/deactivates auto balancing for the whole
system
DPT_Enable R R R/W
Cooling Activation (Auto/H/C) Controls the running mode of the whole
system
DPT_Switch R R R/W
Eco Override Will force ECO mode, same function as used with R-56 DPT_HVACMode R R/W R/W
Supply Alarm Activation Activates/deactivates supply diagnostic for the C-56 DPT_Enable R R R/W